Product catalog summary
Overview:
The document provides specifications and requirements for differential pressure systems used in smoke and heat control of escape routes, as per DIN EN 12101-6:2005. This standard has been mandatory since April 1, 2007, and is crucial for ensuring safe evacuation routes in buildings.

Key Specifications:
  • Door Opening Force: Maximum force to open doors is 100 N.
  • Control-System Acting Time: The system must reach 90% of volumetric requirements within 3 seconds.
  • Air Velocity: Maintain defined air velocity between the pressurized zone and the fire storey.

System Components:
  • Includes stabilized axial-flow fan, control valve, multi-blade dampers with SLC drive, weather protection grille, smoke detectors, manual alarm boxes, and EKS control system tested by VdS.

Quality Assurance:
  • Mechanical parts are tested for 10,000 cycles of loading followed by functional testing.
  • Twelve-month weather testing for all mechanical parts.

System Examples:
  • Mechanical air supply and exhaust systems designed for pressure control and smoke management.
  • Systems to prevent smoke entry into staircases and manage pressure losses.

Advantages:
  • Prevents smoke from entering staircases.
  • Minimizes wind and convection influences.

Technical Data:
  • Specifications for DV1 supply air fans and RK2-JZI-DS-AH pressure relief units, including dimensions, weight, and volume flow rates.
Specifications:
The document details specifications for the RK2-H-JZI pressure relief unit for wall and floor installation, including optional accessories like a baffle plate. It provides dimensions and volume flow rates for various RK2-H model sizes, with measurements for outside dimensions, total weight, and recommended wall penetration sizes.

Fire Resistance and Smoke Extraction:
Specifications include fire resistance classes and functional endurance times for smoke extraction ducts made of sheet steel. The EK-90 fire resistance class offers 90 minutes of fire resistance, with functional endurance of 60 minutes at 600°C or 120 minutes at 400°C. Self-supporting, fire-resistant smoke extraction ducts have a functional endurance of 120 minutes at 600°C.

Fire Prevention Standards:
References fire prevention standards such as K90 or K30 dampers in accordance with DIN 4102-6 and smoke exhaust systems standards from Part III – 03/2007.

Contact Information:
Contact details for Strulik GmbH and its international partners in countries including Germany, Austria, France, Hungary, Ireland, Iceland, Italy, Netherlands, Poland, Switzerland, Turkey, and the United Kingdom.
See more

Catalog excerpts

Fire Prevention Part V-1

Fire Prevention Part V – 4/2007 Differential pressure systems Smoke and heat control of escape routes in accordance with DIN EN 12101-6

 Open the catalog to page 1
Fire Prevention Part V-2

DIN EN 12101-6:2005 Smoke and heat control Part 6: Provisions for differential pressure systems – kits DIN EN 12101-6 is a mandated harmonized standard. Announcement in the Official Journal of the EC: 2005-12-14 / Publication in the Federal Official Gazette / Gazette of Coexistence phase until Thus as from 1st April 2007 DIN EN 12101-6 will be established law and applicable to differential pressure systems. This means: Differential pressure systems shall meet the following requirements on principle: Door opening force: Differential pressure systems shall be designed such that the door opening...

 Open the catalog to page 2
Fire Prevention Part V-3

The term "kit": stabilized axial-flow fan and control valve Opening moment Closing moment

 Open the catalog to page 3
Fire Prevention Part V-4

Quality assurance Testing chamber

 Open the catalog to page 4
Fire Prevention Part V-5

Quality assurance Control valve systems 10.000 cycles loading of all mechanical parts, afterwards functional testing Twelve-month weather testing of all mechanical parts 4

 Open the catalog to page 5
Fire Prevention Part V-6

Quality assurance System safety EKS-D control Line Smoke control exhaust device smoke detector and manual alarm box control damper (SLC) monitored oke control press monitored Multi-blade damp monitored Building control technology contacts monitored monitored Fire alarm system

 Open the catalog to page 6
Fire Prevention Part V-7

Differential pressure systems Smoke control pressure device with an integral automatical control valve Type: DV-RK1 Discharge fan with an integral automatical control valve Type: DV-RK2-EV Smoke control pressure device Type: DV1 Automatical control valve Type: RK2 Automatical discharge unit Type: RK2-JZI-DS-AH

 Open the catalog to page 7
Fire Prevention Part V-8

The permissible pressure difference Ap in Pa (diagram 1) is determined by the appropriate door surface. The pressure difference supplies the energy for the flow through the open The achieved velocity does not allow smoke to flow into the staircase at certain temperatures (diagram 2). Velocity through the door in m/s

 Open the catalog to page 8
Fire Prevention Part V-9

Differential pressure systems System example: Mechanical air supply with DV-RK1 Mechanical air exhaust with DS-RK2-EV RK1 pressure control valves open, staircase door closed RK2 pressure control valves open, exhaust fan DV in the by-pass mode Components: 1. DV-RK1 supply air device with an integral control valve 2. DS-RK2-EV exhaust ventilator with a roof base and control valve. For a secure discharge independent from the weather factors. 3. Multi-blade damper with SLC drive and weather protection grille for the wake 4. RKI-90 SLC smoke control damper 5. Appropriate number of ST-P-DA-STB ceiling...

 Open the catalog to page 9
Fire Prevention Part V-10

Differential pressure systems System example: Mechanical air supply with DV-RK1 Mechanical air exhaust with DS-RK2-EV RK1 pressure control valves closed, staircase door open RK2 pressure control valves closed, exhaust fan DV during nominal operation Components: 1. DV-RK1 box device with an integral control valve 2. DS-RK2-EV exhaust ventilator with a roof base and control valve. For a secure discharge independent from the weather factors. 3. Multi-blade damper with SLC drive and weather protection grille for the wake 4. RKI-90 SLC smoke control damper 5. Appropriate number of ST-P-DA-STB ceiling...

 Open the catalog to page 10
Fire Prevention Part V-11

Differential pressure systems System example: Mechanical air supply with DV1 RK2-JZI-DS-AH discharge unit with pressure control valve Natural discharge in the fire level RK2 pressure control valves open, staircase door closed Facade discharge area open Components: 1. DV1 supply air fan as a box device 2. Pressure relief unit with integral RK2 control valve and powered JZI (SLC) multi-blade damper 3. Multi-blade damper (SLC drive) with a weather protection grille for the wake 4. Appropriate number of ST-P-DA-STB ceiling smoke detectors First detection row 5. Appropriate number of ST-P-DA-STB ceiling...

 Open the catalog to page 11
Fire Prevention Part V-12

Differential pressure systems System example: Mechanical air supply with DV1 RK2-JZI-DS-AH discharge unit with pressure control valve Natural discharge in the fire level RK2 pressure control valves closed, staircase door and facade discharge area open Components: 1. DV1 box device 2. Pressure relief unit with integral RK2 control valve and powered JZI (SLC) multi-blade damper 3. Multi-blade damper (SLC drive) with a weather protection grille for the wake 4. Appropriate number of ST-P-DA-STB ceiling smoke detectors First detection row 5. Appropriate number of ST-P-DA-STB ceiling smoke detectors...

 Open the catalog to page 12
Fire Prevention Part V-13

Differential pressure systems System example: Mechanical air supply with DV1 RK2-JZI-DS-AH discharge unit with pressure control valve Overflow between floodgate and elevator lobby, all floors with the same preference regarding the flow-through RK2 pressure control valve open, staircase doors closed and facade discharge area open Discharge elevator shaft These areas determine the leakage flow rate 2. Pressure relief unit with integral RK2 control valve and powered JZI (SLC) multi-blade damper 3. Multi-blade damper (SLC drive) with a weather protection grille for the wake 4. Appropriate number...

 Open the catalog to page 13
Fire Prevention Part V-14

Differential pressure systems System example: Mechanical air supply with DV1 RK2-JZI-DS-AH discharge unit with pressure control valve Overflow between floodgate and elevator lobby, all floor with the same preference regarding the flow-through RK2 pressure control valve closed, staircase doors closed and fire room door as well as facade discharge area open Discharge elevator shaft These areas determine the leakage flow rate 2. Pressure relief unit with integral RK2 control valve and powered JZI (SLC) multi-blade damper 3. Multi-blade damper (SLC drive) with a weather protection grille for the...

 Open the catalog to page 14
Fire Prevention Part V-15

DV1 – supply air fan as a box device Accessories: 1. Protection grille: at the suction side or at the pressure side 2. Elastic spigot: at the suction side or at the pressure side 3. Multi-blade damper with a SFR 1.90SLC drive – affixed at the pressure side 4. Repair switch in the direction of flow – affixed at the top, at the side (on the left/right side) * Rubber vibration damper included in the scope of delivery Main dimensions (mm) Type

 Open the catalog to page 15