BCF-2-K90
19Pages

{{requestButtons}}

Catalog excerpts

BCF-2-K90 - 1

Accessories (optional): MS-C - electrical limit switch VMT - disk valve for overflow opening NW 100/125/160 or 200 Mounting frame for installation into: Resistance class K90/K30 in accordance with DIN 4102-6 - light partitions, brickwork or concrete floors - as above, however lengthened, L = 140 mm - F30/F90 supplement floors, shaft walls or classified ducts, L = 140 mm - as above, however in short version for a floor thickness ≤ 30 mm - solid walls (dry mounting) - massive floors and supplement floors (dry mounting) - light partition walls (dry mounting) For the installation into a F30 supplement floor. If the mounting frame and floor thickness have not been specified, the KKL-ZX will be delivered with loose angles for fastening) Important features • The Strulik BCF-2-K90 damper ideally combines the function of an infinitely variable supply and exhaust air valve with the fully effective properties of a damper having a K90 resistance class. • The damper is mounted directly into the fire-protected zone. Thus the disk valve itself guarantees the effectiveness of fire protection. • No special fixing arrangements are required (i.e. saving of time and high economy). • Strulik dampers may even be mounted subsequently into ventilation systems, in order to meet the effective fire prevention requirements. Essential features 1/ Safety classification. • Official classification: Resistance class K90 • Maximum sealing 2/ Low noise level • Ideal aerodynamic characteristics • Maximum insulation • The damper is fully integrated within disk valve and therefore does interfere with the through-flow of (ideal balancing ratio between volume and noise level). Please note: For examples of application, see BTZ-2 on page 111 - 115, 117 - 121 and for technical data, see page 124 - 126. 3/ Adjustment of air volume • Infinitely variable control of all required air volumes Safety The Strulik BCF-K90 dampers have been submitted to many test series in Germany and abroad. These test series did not only include the effectiveness of FIRE PROTECTION and FLAME TIGHTNESS, but also the STABILITY OF FLAMES and the correct functioning of the FUSIBLE LINK (see additional test certificate from the "Verband der Sachversicherer" in Cologne). In Germany the damper has been tested against fire and smoke in accordance with the principles of construction and testing of the "Deutsches Institut für Bautechnik" in Berlin. The expert opinion for a K90 resistance class has been prepared by the "Institut für Haustechnik" of the Technical University of Munich. VdS in Cologne has prepared the test report on the release mechanism for an activation temperature of 72 °C in acc

Open the catalog to page 1
BCF-2-K90 - 2

Test certificate Pressure drop and noise level The Strulik damper allows an infinitely variable control of any required air volume. The adjustment is made according to the accompanying diagram. The valve core is locked with a counter nut in the chosen Volume flow rate m3/h

Open the catalog to page 2
BCF-2-K90 - 3

* Installation into - floors of concrete (min. 100 mm) - walls of brickwork (min. 115 mm) - walls of gas-formed concrete (min. 100 mm) - wall panels (min. 80 mm) in accordance with DIN 18163 Resistance class K90/K30 For the installation into brickwork or a concrete floor Standard spirally wound duct *) Installation detail: KKS mounting frame KKS mounting frame *) The mounting frame shall be riveted from the inside with steel rivets 3x6 within the standard spirally wound duct. Fill surrounding gap with mortar of group II and III, DIN 1053 or with gypsum WFR plastered flush with the wall or...

Open the catalog to page 3
BCF-2-K90 - 4

Installation into light partition walls in accordance with DIN 4102-4 Lost formwork of min. 12,5 mm fireproofing boards Fit in the hull and brush and smooth with gap filler Resistance class K90/K30 For the subsequent installation into light F30-F90 partition walls Alternatively with a C profile by the installer Lost formwork of min. 20 mm fireproofing boards The mounting frame shall be riveted from the inside with steel rivets 3x6 to the standard spirally wound duct Wooden screw by the installer By the installer: Doubling of fireproofing boards for mounting into shaft walls ≤ 80 mm (F90)...

Open the catalog to page 4
BCF-2-K90 - 5

Test certificate fire resistant ventilation ducts mounting frame Three steel Depending on the wall thickness x, double For the installation into F30 fire resistant suspended ceilings, laid-in floor X = according to the required plate thickness of the floor. Please state when Technical data Installation into suspended F30 ceilings in accordance with the table on page 186 for type A + D and suspended metal ceilings in accordance with the test certificate. Installation into fire resistant L30 - L90 ventilation ducts Installation into cable conduits Installation into fire resistant suspended...

Open the catalog to page 5
BCF-2-K90 - 6

Installation of a BTZ-K30U into an OWAcoustic F30 DUO floor as a laid-in floor, see table on page 186, type A KKL-ZX mounting frame Flexible aluminium duct (A DIN 4102)* Test certificate Z-41.3-549 Resistance class K30U For the installation into fire resistant suspended F30 DUO ceilings as laid-in floor Three steel angles 60x20, staggered by 120° and screwed to the floor Fireproofing boards, 20 mm thick x = according to the required plate thickness of the floor. Please state when ordering. Scope of delivery from Strulik or by the installer. * not part of the scope of delivery Installation...

Open the catalog to page 6
BCF-2-K90 - 7

Installation into fire resistant suspended F30 ceilings as a metal floor KKL-ZX mounting frame Flexible aluminium duct (A DIN 4102)* Resistance class K30U For the installation into suspended metal F30 ceilings Three steel angles 60x20, staggered by 120° and screwed to the floor in accordance with the test certificates Ø D+10 Metal floor section * not part of the scope of delivery Installation into fire resistant suspended metal DIPLING F30 ceilings Section Ø D+40 KKL-ZX mounting frame Flexible aluminium duct (A DIN 4102)* Three steel angles 60x20, staggered by 120° and screwed to the floor...

Open the catalog to page 7