1. Catalogs
  2. SICK SENSOR INTELLIGENCE
  3. GM35 In-Situ IR Gas Analyzer
video corpo

GM35 In-Situ IR Gas Analyzer

GM35 In-Situ IR Gas Analyzer
1 / 16 PagesView full catalog

GM35 In-Situ IR Gas Analyzer

Product catalog summary
Overview: The GM35 In-Situ IR Gas Analyzer by SICK is engineered for the measurement of CO2, H2O, and CO or N2O directly in gas ducts, offering easy installation, low maintenance, and quick response times without complex gas sampling.

Key Features:
  • Measures multiple gas components, temperature, and pressure simultaneously.
  • Features dynamic humidity correction and rapid in-situ measurement.
  • Includes integrated self-test and control functions.
  • Available in cross-duct and measuring probe versions.

Applications:
  • Used for emission monitoring in power and cement plants.
  • Monitors combustion efficiency in hazardous waste incineration.
  • Applicable in urea production process monitoring and heat exchanger tube rupture detection.

Technical Specifications:
  • Measurement ranges: CO (0-180 ppm / 0-20,000 ppm), CO2 (0-22.5 Vol.-% / 0-100 Vol.-%), H2O (0-25 Vol.-% / 0-100 Vol.-%), N2O (0-60 ppm / 0-2,500 ppm).
  • Zero and reference point drift within ±2% of the measuring range.
  • Operating temperature range: -40°C to +55°C.
  • Conforms to EN 14181, EN 15267, and CE electrical safety standards.

Components:
  • Sender/Receiver Unit: IP 65/NEMA 4x rated, CAN bus protocol, dimensions 291 mm x 527 mm x 529 mm.
  • Open Measuring Probe (GMP): Suitable for process temperatures up to +430°C, dust load up to 3 g/m³.
  • Gas-Testable Measuring Probe (GPP): Suitable for high dust concentrations, process temperatures up to +430°C.
  • Reflector Unit: Hollow triple reflector, process temperature up to +500°C.
  • Evaluation Unit: Available in steel sheet or cast metal enclosure, IP 65 or IP 67 rated, with multiple analog and digital outputs.

Specifications and Dimensions: Detailed dimensions for weather hoods are provided, including diameters and lengths in millimeters and inches.

Services Offered: SICK provides LifeTime Services, including consulting, training, upgrades, retrofits, verification, optimization, and support, ensuring practical, safe, economical, and reliable solutions.

Online Services: Customers can register on the SICK website to access product selection, wish lists, net prices, order tracking, and email notifications.

Company Overview: SICK is a global leader in intelligent sensors and solutions for industrial applications, with a presence in over 50 countries, offering tailored solutions through its application centers.

Global Presence: SICK operates worldwide with offices in countries such as Australia, Brazil, China, Germany, India, Japan, and the USA. More details are available on their website.
See more

Catalog excerpts

GM35 In-Situ IR Gas Analyzer-1

SIMULTANEOUS OR INDIVIDUAL MEASUREMENT OF CO2, H2O AND CO OR N2O In-situ gas analyzer

 Open the catalog to page 1
GM35 In-Situ IR Gas Analyzer-2

Efficient control of combustion and drying processes Efficient control of process-relevant parameters is important for controlling and regulating combustion or drying processes. Apart from oxygen, mainly CO must be reliably and exactly measured. In drying processes, the humidity curve during the process must be acquired and the plants monitored for CO concentrations. The in-situ gas analyzer GM35 from SICK is predestined for this purpose because it measures CO, CO2 and H2O simultaneously and directly in the process. Moreover, monitoring and reducing greenhouse gas emissions in industrial plants...

 Open the catalog to page 2
GM35 In-Situ IR Gas Analyzer-3

In-situ Gas analyzer GM35 Measuring probe version Sender/receiver unit with measuring probe. Two measuring probe types with integrated temperature and pressure sensors are available: • GMP measuring probe with open measuring path • Single-side duct access and simple installation • Integrated zero point path • Application adaptation, independent from duct dimensions • Versatile use, suitable for dust concentrations up to 3 g/m3 • Cost-efficient to purchase Sender/receiver unit • Single-side duct access • Suitable for applications with high dust concentrations • Integrated zero point path • Application...

 Open the catalog to page 3
GM35 In-Situ IR Gas Analyzer-4

EFFICIENT CONTROL OF COMBUSTION AND DEHYDRATION PROCESSES Additional information Product description Simultaneous or individual measure- trations as well as temperature and pressure quickly, easily and economi- cally. The in-situ measurement technol- • Dynamic humidity correction • Fast in-situ measurement directly in three gas components, temperature Your benefits • Dynamic humidity measurement • Provision of real humidity reference • Unbiased measured values due to in-situ measurement values directly in the gas-carrying duct without gas sampling. Reliability, accuracy and short response time...

 Open the catalog to page 4
GM35 In-Situ IR Gas Analyzer-5

In-situ gas analyzers GM35 Fields of application • Emission monitoring according to EN 14181, e.g. • Monitoring of combustion efficiency in hazardous in power or cement plants • Control of the water-injection upstream of the electrostatic precipitator • Process monitoring in urea production • Tube rupture detection in heat exchangers waste incineration Detailed technical data The exact device specifications and performance data of the product may deviate from the information provided here, and depend on the application in which the product is being used and the relevant customer specifications....

 Open the catalog to page 5
GM35 In-Situ IR Gas Analyzer-6

GM35 In-situ gas analyzers Sender/receiver unit Description Analyzer unit of the measuring system Enclosure rating Electrical connection Voltage Frequency Power consumption Open measuring probe (GMP) Description Measuring probe in open design with integrated purge air control system Process temperature Process pressure ≤ 120 hPa Depending on purge air supply Dust load Measuring probe: ≤ ± 25 kg Purge air fixture: ≤ ± 7 kg Material in contact with media Stainless steel 1.4571, stainless steel 1.4539 Auxiliary connections Integrated components Pressure sensor PT1000 temperature sensor Gas-testable...

 Open the catalog to page 6
GM35 In-Situ IR Gas Analyzer-7

In-situ gas analyzers GM35 Reflector unit Description Reflector unit with hollow triple reflector Process temperature Process pressure Depending on purge air supply GM35 evaluation unit: steel sheet enclosure Description The evaluation unit serves as user interface and is responsible for data processing and output as well as control and monitoring functions Enclosure rating Analog outputs Analog inputs Digital outputs Digital inputs 3 inputs: 24 V Preset for failure, maintenance and functional control LC display Status LEDs: “Power”, “Maintenance” and “Fault” Arrow keys Functional keys Menu-driven...

 Open the catalog to page 7
GM35 In-Situ IR Gas Analyzer-8

LC display Status LEDs: “Power”, “Maintenance” and “Fault” Arrow keys Functional keys Menu-driven operation via LC-display and membrane keyboard Cast metal enclosure Electrical connection Voltage Power consumption Connection unit Description To lengthen the internal CAN-Bus connection with cable provided by the customer Purge air fixture: sender/receiver unit Description Fixture to flanges with connections for purge air and external cabelling Auxiliary connections Integrated components PT1000 temperature sensor Pressure sensor Purge air fixture: reflector unit Description Auxiliary connections...

 Open the catalog to page 8
GM35 In-Situ IR Gas Analyzer-9

In-situ gas analyzers GM35 Ordering information Our regional sales organization will help you to select the optimum device configuration. Dimensional drawings (Dimensions in mm (inch)) GM35 sender/receiver unit 8009253/2015-11 Subject to change without notice

 Open the catalog to page 9
GM35 In-Situ IR Gas Analyzer-10

GM35 In-situ gas analyzers Gas-testable measuring probe (GPP) L1 227 (8.94) 10 (0.39) Measuring gap L3 (active measuring path) 227 (8.94) Probe length, nominal All dimensions in mm (inch) Application specific lengths on request

 Open the catalog to page 10
GM35 In-Situ IR Gas Analyzer-11

In-situ gas analyzers GM35 Open measuring probe (GMP) L1 L3 Measuring gap L3 (active measuring path) 250 (9.84) Probe length, nominal All dimensions in mm (inch) Application specific lengths on request

 Open the catalog to page 11
GM35 In-Situ IR Gas Analyzer-12

8009253/2015-11 Subject to change withou

 Open the catalog to page 12
GM35 In-Situ IR Gas Analyzer-13

In-situ gas analyzers GM35 GM35 AWE evaluation unit: cast metal enclosure 8009253/2015-11 Subject to change without notice

 Open the catalog to page 13
GM35 In-Situ IR Gas Analyzer-14

GM35 In-situ gas analyzers Mounting flange, Di=125 mm 3 (0.12) Weather hood for reflector unit Weather hood for sender/receiver unit 576.3 (22.69) 525.8 (20.7)

 Open the catalog to page 14
GM35 In-Situ IR Gas Analyzer-15

REGISTER AT WWW.SICK.COM TODAY AND ENJOY ALL THE BENEFITS m Select products, accessories, documentation and software quickly and easily. Create, save and share personalized wish lists. Overview of all quotations and orders. View the status of quotations and orders at any time. Receive e-mail notifications of status changes. Easily repeat previous orders. View the net price and date of delivery for every product. Requests for quotation, ordering and delivery tracking made easy. Direct ordering: submit even very complex orders in moments. Conveniently export quotations and orders to work with...

 Open the catalog to page 15

All SICK SENSOR INTELLIGENCE catalogs and technical brochures

  1. WE9LC-3_A71

    3  Pages

  2. Safety Switches

    20  Pages

  3. Distance Sensors

    404  Pages

  4. Vision

    124  Pages

  5. Fluid Sensors

    243  Pages

  6. ConVer

    12  Pages

  7. Encoders

    788  Pages

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.