CPCI AC 300W

CPCI AC 300W

CPCI AC 300W

Product catalog summary
Specifications:
  • Input Voltage: 485-265Vac or 100-350Vdc
  • Output Power: 300W
  • Power Factor Correction: EN61000-3-2 compliant
  • Size: 3U x 8TE x 160mm
  • Safety Standards: IEC/EN 62368-1, RoHS compliant
Features:
  • Active very low inrush current limitation
  • Surge and transient protection
  • Current sharing and N+1 redundancy
  • LED indicators for status
  • Short-circuit proof outputs
Procedures:
  • Input is protected against surges and transients with EMI filtering.
  • Outputs are continuously protected against short-circuit by a constant current limitation.
  • Thermal protection disables output when heatsink temperature exceeds 90°C and restarts below 55°C.
  • Parallel operation is possible for V1, V2 with active current sharing.
Norms and Standards:
  • Meets MIL-STD 461E CE102, MIL-STD 1399-300A, MIL-STD810E for shock and vibrations.
  • Qualified for EN 61000-4 -2, -3, -4, -5, -6, -11, EN 61000-3-2, EN 61000-3-3.
Recommendations:
  • Ensure sufficient airflow for convection cooling.
  • Do not open converters to maintain warranty.
  • Connect pin 45 (Earth) to the protective earth of the supply system.
Options:
  • Conformal coating for high humidity applications.
  • Common mode surge protection with 61000-4-5 Level 3 2KV.
See more

Catalog excerpts

CPCI AC 300W-1

AC-DC CompactPCI® Features 485-265Vac or 100-350Vdc input voltage ranges 44 outputs 4Output power 300W 4Power Factor Correction EN61000-3-2 4Active very low inrush limitation 4Surge and transient protection 4Current sharing & N+1 redundancy 43U x 8TE x 160mm Safety IEC/EN 62368-1, RoHS lead-free-solder compliant The CPCI AC, AC-DC CompactPCI® compliant with PICMG 2.11 standard, incorporates input and output protections and filtering, signalling features, required in severe environments for industrial, defense, avionic applications. The PSU provides significant advantages, high reliability thanks to the integration of Vicor Corp. modules, high efficiency, low ripple and noise levels, input-to-output isolation, soft start, MOFSET based active very low inrush limitation circuit, overtemperature protection, input over/undervoltage lockout. The input is protected against surges and transients and EMI filtered. The outputs are countinuously short-circuit proof. LEDs in front panel indicates the status of the psu. Carte commande CDPFCC Schéma électrique CDPFCC Regulation and current sharing PFC and inrush current control board Regulation and current sharing EMI filtering, Active Inrush current limiting and PFC FAIL IPMB_PWR Protection and Control board -VOUT Remote On/Off -VIN -VOUT Remote On/Off

 Open the catalog to page 1
CPCI AC 300W-2

f^^_Options Description MIL-STD ruggedized (M) Meet MIL-STD 461E CE102, MIL-STD 1399-300A, MIL-STD810E shock & vibrations. Laboratory certification. -40°C operation (T) The thermal grade of the Vicor the DC/DC converters used and other components are changed to comply with low ambiant temperature. Conformal coating (V) During manufacturing process , when V option is specified, components and pcb are covered with an acrylic coating to address high level of ambiant humidity application. 61000-4-5 (Y) Include a common mode surge protection 61000-4-5 Level 3 2KV based on gas discharger and VDR to...

 Open the catalog to page 2
CPCI AC 300W-3

Parallel operation & current share Hold up time Parrallel operating is possible for V1, V2 with active current sharing. The signals SHARE are single wire. All V1 SHARE of the different psu in parrallel will have to be connected together. (Same for V2 SHARE). Redundant Systems Operation When systems require a very high level of reliability and should work normally in the event of a failure, N+1 redundancy is implemented where N is the number of converter to support power requirement. If one converter fail, the remaining ones still delivers the power to the loads. Redundant operation is directly...

 Open the catalog to page 3
CPCI AC 300W-4

Waveforms Inhibit (Remote On/Off) A INH signal activate & de-activate the output voltages - outputs inhibited : INH level LOW Output Voltage Adjustment The converter outputs can be factory adjustable to different values than standard ones. Consult factory. Sense Lines This feature enables compensation of voltage drop across the connector contacts and the load lines. This fonctionnality is implemented on V1 & V2 only. The voltage between any sense line and its respective power output pin (as measured on the connector) should not exceed the following values at nominal output voltage. EN# signal...

 Open the catalog to page 4
CPCI AC 300W-5

f^^_Electromagnetic Electromagnetic Immunity CPCI AC Rev. 01 Page 5 of 9 www.powersystemtechnology.com

 Open the catalog to page 5
CPCI AC 300W-6

Mechanical data Size : 3U x 8TE x 160mm Solder side of the PCB protected by PBT sheet. Weight : 600g Product label

 Open the catalog to page 6
CPCI AC 300W-7

CPCI AC Rev. 01 Page 7 of 9 www.powersystemtechnology.com

 Open the catalog to page 7
CPCI AC 300W-8

Cleaning Agents and Process The converters are not hermetically sealed. In order to avoid possible damage, any penetration of liquids shall be avoided. Isolation The electric strength test is performed in the factory in accordance with IEC/EN 62368-1. f^^_Safety & Installation These converters are components, intended exclusively for integration into other equipment by an industrial assembly process or by a professionally competent person. Installation must strictly follow the safety regulations in respect of the enclosure, mounting, creepage and clearance distances, markings of the end-use application....

 Open the catalog to page 8
CPCI AC 300W-9

Options and configurations Max. power available : 300W IN max : see table page 2

 Open the catalog to page 9

All POWER SYSTEM TECHNOLOGY catalogs and technical brochures

  1. PST21D

    11  Pages

  2. PST14

    20  Pages

  3. PST14X 320W

    12  Pages

  4. PST21A

    13  Pages

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.