Product catalog summary
Overview: This document provides comprehensive details on the DRE pressure controller, which is engineered for effective line pressure management in ventilation and air-conditioning systems. It covers the product's specifications, features, installation instructions, and technical data.
Specifications: The DRE pressure controller is capable of managing differential pressures up to 1000 Pa, with minimal air leakage as per DIN EN 1751, class 4. It boasts housing tightness class C and eliminates the need for a flow path, resulting in reduced pressure losses and energy efficiency.
Design and Features: The controller is equipped with a housing that includes a damper blade, a control unit with a differential pressure sensor, and an actuator. Optional insulation shells are available for both acoustic and thermal insulation. The design facilitates easy installation with pre-assembled components.
Functionality: The DRE ensures constant inlet pressure by comparing the actual pressure with a preset setpoint and adjusting the damper blade accordingly, promoting stable pressure distribution and efficient fan control.
Installation Guidelines: Proper positioning of the pressure tap is crucial to avoid flow disturbances. The controller should be installed with the damper axis horizontally, and adjustments for height and hose length must be made for the differential pressure sensor.
Technical Data: Detailed technical data is provided, including power supply requirements, connection types, and parameterization options. The controller supports both analogue and digital inputs and outputs and is compatible with Modbus RTU.
Acoustic Data: The document includes tables that detail airborne sound transmission and structure-borne noise emission, offering sound power levels across various frequencies and conditions.
Applications: The DRE is applicable for both supply and extract air circuits in ventilation systems, with examples given for use in open-plan offices and individual rooms.
Ordering Information: The brochure provides nomenclature and order codes for specifying the desired configuration of the DRE pressure controller, including size, design, insulation options, and control settings.
See more

Catalog excerpts

DRE-1

Let‘s realize the potential of air for a sustainable world Technical brochure Pressure controller DRE The DRE pressure controller offers an efficient, precise and cost-effective solution for line pressure control in ventilation and air-conditioning systems. It is ideal wherever a constant pressure is required in air pipes without the need for measurement of the air flow rate. Differential pressure control up to 1000 Pa Air leakage rate according to DIN EN 1751, class 4 (DN 100/125: class 3) Housing tightness class C accord. to DIN EN 1751 No flow path required Low pressure losses: Energy savings, quiet operation Precise line pressure control for stable operating conditions Measuring range: 0...500 Pa depending on version Conversion or programming to DREactive or VREactive is possible Compact design, retrofittable insulation shell W W W . L T G - A G . COM

 Open the catalog to page 1
DRE-2

LTG Comfort Air Technology | Technical brochure Pressure controller DRE, round Application range, design, features, materials and finishes, optional versions, 3 accessories and special versions Function, installation, positioning 4 Ventilation systems with pressure controllers 7 Nomenclature, ordering code 8 Technical data, controller components 9 © LTG Aktiengesellschaft, Grenzstrasse 7, 70435 Stuttgart , Germany Tel. +49 711 8201-0, Fax +49 711 8201-720, [email protected], www.LTG-AG.com Previous editions are invalid. Subject to technical changes.

 Open the catalog to page 2
DRE-3

LTG Comfort Air Technology | Technical brochure Pressure controller DRE, round Application range The DRE pressure controller is used for line pressure control in air pipes within ventilation and air-conditioning systems. It ensures that a constant and defined inlet pressure is maintained at downstream components such as air flow controllers, induction units or air diffusers. This automatically balances the air circuits and achieves optimised pressure distribution throughout the entire system. The measured pressure value can be used, taking the damper position into account, to control the fan...

 Open the catalog to page 3
DRE-4

LTG Comfort Air Technology | Technical brochure Pressure controller DRE, round Installation, positioning How does the DRE work? The static pressure in the air duct is detected via a pressure tap at the desired measuring point and measured by the differential pressure sensor. The controller compares the actual pressure with the preset setpoint and controls the damper blade so that the setpoint is maintained as accurately as possible. This control principle ensures stable pressure distribution throughout the duct network and contributes to efficient fan control. 2 The DRE pressure controller itself...

 Open the catalog to page 4
DRE-5

LTG Comfort Air Technology | Technical brochure Pressure controller DRE, round © LTG Aktiengesellschaft, Grenzstrasse 7, 70435 Stuttgart , Germany Tel. +49 711 8201-0, Fax +49 711 8201-720, [email protected], www.LTG-AG.com Previous editions are invalid. Subject to technical changes.

 Open the catalog to page 5
DRE-6

LTG Comfort Air Technology | Technical brochure Pressure controller DRE, round © LTG Aktiengesellschaft, Grenzstrasse 7, 70435 Stuttgart , Germany Tel. +49 711 8201-0, Fax +49 711 8201-720, [email protected], www.LTG-AG.com Previous editions are invalid. Subject to technical changes.

 Open the catalog to page 6
DRE-7

LTG Comfort Air Technology | Technical brochure Pressure controller DRE, round DRE Ventilation systems with pressure controllers (examples) The pressure setpoint must be designed in accordance with the downstream loads. A calculation of the air duct network is essential. Ventilation systems with pressure controllers in the supply air and extract air circuits Line pressure controller 24 V A: for open-plan offices Extract air diffuser B: for individual rooms Transfer air diffuser LDO Line pressure controller 24 V 7 Line pressure controller 24 V DRE A: for open-plan offices Extract air diffuser...

 Open the catalog to page 7
DRE-8

LTG Comfort Air Technology | Technical brochure Pressure controller DRE, round DRE = Pressure controller, round, short Please specify when ordering: - Control: Analogue or Modbus If this information is not provided, the unit will be supplied with the following factory setting: - Analogue control Ordering example DRE 100/S/D/L/G710, Pmin = 150 Pa, Pmax = 300 Pa, 2...10 V mode, Modbus control © LTG Aktiengesellschaft, Grenzstrasse 7, 70435 Stuttgart , Germany Tel. +49 711 8201-0, Fax +49 711 8201-720, [email protected], www.LTG-AG.com Previous editions are invalid. Subject to technical changes.

 Open the catalog to page 8
DRE-9

LTG Comfort Air Technology | Technical brochure Pressure controller DRE, round © LTG Aktiengesellschaft, Grenzstrasse 7, 70435 Stuttgart , Germany Tel. +49 711 8201-0, Fax +49 711 8201-720, [email protected], www.LTG-AG.com Previous editions are invalid. Subject to technical changes.

 Open the catalog to page 9
DRE-10

LTG Comfort Air Technology | Technical brochure Pressure controller DRE, round © LTG Aktiengesellschaft, Grenzstrasse 7, 70435 Stuttgart , Germany Tel. +49 711 8201-0, Fax +49 711 8201-720, [email protected], www.LTG-AG.com Previous editions are invalid. Subject to technical changes.

 Open the catalog to page 10
DRE-11

LTG Comfort Air Technology | Technical brochure Pressure controller DRE, round Aptot " Total pressure difference fm - Octave midband frequency Lw - Sound power level Lwa - Sound power level, A-weighted LpA - Sound pressure level, A-weighted © LTG Aktiengesellschaft, Grenzstrasse 7, 70435 Stuttgart , Germany DRE_eng_TP (07/26) Tel. +49 711 8201-0, Fax +49 711 8201-720, [email protected], www.LTG-AG.com Previous editions are invalid. Subject to technical changes.

 Open the catalog to page 11
DRE-12

LTG Comfort Air Technology | Technical brochure Pressure controller DRE, round APtot - Total pressure difference fm - Octave midband frequency Lw - Sound power level Lwa - Sound power level, A-weighted LpA - Sound pressure level, A-weighted The values for structure-borne noise emission refer to the emitting outer surface of an air duct, including a built-in flow rate controller made of galvanised sheet steel, with a total length of 6 m. Resonance effects may cause deviations of up to ± 6 dB in frequency-dependent sound power levels. © LTG Aktiengesellschaft, Grenzstrasse 7, 70435 Stuttgart ,...

 Open the catalog to page 12

All LTG Incorporated catalogs and technical brochures

  1. Type Series VQF

    46  Pages

  2. LTG Prefilter

    8  Pages

  3. VRF active

    16  Pages

  4. DRF

    18  Pages

  5. DREactive

    17  Pages

  6. DRFactive

    22  Pages

  7. VSR 5./RU..MS

    18  Pages

  8. LTG

    12  Pages

  9. KLB

    8  Pages

  10. HFF

    2  Pages

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.
About AeroExpo
AeroExpo is a marketplace that offers B2B players a complete experience, from product sourcing to purchase. AeroExpo is an entity of VirtualExpo Group.