Catalog excerpts
Remote Actuator Unit (RAU) with Lockout for DD-Frame (D5) Remote actuator unit is factory-fitted on the left hand side of the DD-Frame circuit breaker The RAU module is designed to function on a wide voltage range: 18 Vdc to 80 Vdc The RAU can be supplied from the main system voltage or a standalone source The DD-Frame circuit breaker operates on the main system voltage, AC or DC LED for status indication Selectable remote or manual operation Provides status of the load side of the circuit breaker Remote switching operation requires a high or low signal Colour indicator for state of circuit breaker red (ON) or green (OFF) Actuation of circuit breaker occurs internally Compact size (19 mm, matching DD-frame outline) Can be paired with up to a 3 pole DD-frame circuit breaker Device can be locked out to prevent manual operation Battery management Telecommunications Railways Solar System automation Switching operations in distant, inconvenient, or unreachable environments The remote actuation unit (RAU) is a factory-fitted module that enables the automated switching of a DD-Frame circuit breaker. The RAU internally actuates the circuit breaker both ON and OFF. The RAU is mounted on the left hand side of the circuit breaker and can actuate up to three poles. The RAU is available with circuit breakers with a standard toggle handle only. The unit has an LED that provides an indication of the mode of operation (remote or manual) and status. The second is a colour indicator which shows the position of the latching mechanism of the connected circuit breaker - green for OFF and red for ON. The RAU provides the option to set the operation mode between remote or manual. This is selected by a switch situated on the front of the RAU.
Open the catalog to page 1Remote Actuator Unit (RAU) with Lockout for DD-Frame (D5) Technical Data Actuation signal voltage (For other voltages refer to page 11) Starting current Number of poles that can be actuated Ambient operating temperature Typical actuation time Power consumption Number of operations Flammability Toxicity Pollution degree Signal Out Resistance to LOAD terminal Product Type RAU 18 Vdc to 80 Vdc HIGH (ON) Min. 3.3 Vdc to Max. 60 Vdc LOW (OFF) Min. 0.0 Vdc to Max. 0.5 Vdc < 250 mA 1 to 3 pole DD-Frame - factory fitted -20 °C to +65 °C OFF state to ON state 2 seconds ON state to OFF state 1...
Open the catalog to page 2Remote Actuator Unit (RAU) with Lockout for DD-Frame (D5) Ordering Information To order a DD-Frame with RAU, select 7 in Group 2 from the DD-Frame circuit breaker ordering code. Group 1: Frame Group 3: Mounting Group 4: Handle Type or Blank for Reduced Handle Group 5: Termination Description DD-frame Description Lockout Remote actuator unit Description Front mount, rectangular aperture, standard (toggle) handle type Description Comments RAU module attached to DD-frame unit Comments Warning: Maximum penetration depth into the product by the mounting screw is 6 mm Comments Standard handle...
Open the catalog to page 3Remote Actuator Unit (RAU) with Lockout for DD-Frame (D5) Ordering Information Group 10: Circuit Configuration (circuit breaker’s internal construction) Group 11: Auxiliary and Alarm Switches Types & Options Description Switch Circuit breaker (series trip current sensing) Circuit breaker with trip alarm, but NO MID trip (Reversed function - Latch type) Handle goes to OFF position when tripped and send a trip alarm Description Not applicable Gold tips, equally spaced terminals, 2.75 mm, (0.108”) - DB3 Silver tips, equally spaced terminals, 2.75 mm, (0.108”) - DB2 Silver tips, offset...
Open the catalog to page 4Remote Actuator Unit (RAU) with Lockout for DD-Frame (D5) Connection Diagrams LINE 1 ACTUATE SIGNAL HIGH TO SWITCH ON OR LOW TO SWITCH OFF RAU UNIT ACTUATE SIGNAL HIGH OR LOW COMMON GROUND INTELLIGENT CONTROLLER COMMON GROUND SUPPLY VOLTAGE SIGNAL OUT CONNECTED INTERNALLY TO ADJACENT CIRCUIT BREAKER LOAD TERMINAL THROUGH A 330kΩ 2 W RESISTOR FOR USER TO VERIFY IF CIRCUIT BREAKER IS OPEN OR CLOSED RAU UNIT ACTUATE SIGNAL HIGH OR LOW COMMON GROUND SUPPLY VOLTAGE INTELLIGENT CONTROLLER SUPPLY VOLTAGE ACTUATE SIGNAL HIGH OR LOW INTELLIGENT CONTROLLER COMMON GROUND Note: Signal out only provides...
Open the catalog to page 5Remote Actuator Unit (RAU) with Lockout for DD-Frame (D5) Plug compatible with DEGSON 2EDGKF-5.08-04P -14 and a PHOENIX CONTACT plug 1780002. The RAU front switch has two positions, namely ‘‘Remote’’ or ‘‘Manual’’. Refer to table 1 on page 7 for more details. MOUNTING SCREW TERMINALS Installation Instructions 1. Before connecting the RAU to power, the circuit breaker must be in the OFF position and the RAU front switch must be in the REMOTE position. 2. Isolate the power to the circuit breakers. 3. Connect the circuit breakers as required and connect the necessary wiring for the RAU as...
Open the catalog to page 6Remote Actuator Unit (RAU) with Lockout for DD-Frame (D5) Remote Operation Set the front switch to REMOTE to enable remote operation. The LED will be illuminated 1. Switching the circuit breaker ON using the RAU: • Set the actuate signal HIGH. This will switch the circuit breaker ON remotely. While the actuate signal remains in the HIGH state, the circuit breaker can be operated manually like a conventional circuit breaker. 2. Switching the circuit breaker OFF using the RAU: • Set the actuate signal to LOW. This will switch the circuit breaker OFF. While the actuate signal is LOW, the...
Open the catalog to page 7Remote Actuator Unit (RAU) with Lockout for DD-Frame (D5) LED Status Indication LED State Flash 3 times Flash 3 times every 4 seconds ON OFF Blinking 2 Short flash & 1 long flash Indication Initialisation Fault state Remote actuation mode Manual operation mode User will not be able to switch breaker on manually Initialisation fault Application Notes: RAU powered from Negative DC Bus The DD-frame RAU requires a positive supply voltage between 18 Vdc and 80 Vdc to operate, however, systems may only have a negative voltage supply available. The RAU is able to accommodate such environments....
Open the catalog to page 8All LPA CONNECTION SYSTEMS LTD catalogs and technical brochures
-
QA17 -Series Earth Leakages
8 Pages
-
LPA Aircraft Support brochure
13 Pages