1. Catalogs
  2. Layer Electronics
  3. Technical Data ERIX Series

Technical Data ERIX Series

Technical Data ERIX Series

Product catalog summary
Technical Specifications
  • Models: MC-100, MC-102, MC-104, MC-106
  • Power (VA): 1600, 2000, 2500, 3000
  • Input:
    • Phases: 1-Ph
    • Voltage: 220 / 230 / 240 V ± 20% (100 / 110 / 115 / 120 / 127 V on request)
    • Frequency: 50 / 60 Hz ± 5%
  • Output:
    • Wave-form: SINE WAVE
    • Harmonic distortion: < 3%
    • Voltage: 220 / 230 / 240 V ± 2% (100 / 110 / 115 / 120 / 127 V on request)
    • Frequency: 50 / 60 Hz ± 0.5%
    • Overload: 105% for 10 sec., 130% for 300 ms
    • Static switch mains-ups Transfer time: 2 ms
  • Batteries:
    • Type: Sealed lead-acid (NiCd on request)
    • No. Batteries: 2 (12 V 44 Ah) for MC-100/102, 3 (12 V 44 Ah) for MC-104/106
    • Vdc Voltage: 24 for MC-100/102, 36 for MC-104/106
    • Restored energy time: 8 hours for 90% charge level
    • Stored energy time: 40 min
  • Protections: Overload, overtemperature, min/max battery voltage, min/max input voltage, min/max inverter voltage, synchronism, short-circuit with fuse on mains, electronic protection on inverter
  • EMI Suppression: EMI/RFI Filter
  • Signals:
    • LED: Mains, Output, Battery, Overload, Fault
    • Display: Optional
    • Acoustic: Battery mode, low battery, overload, overtemperature, fault
  • Computer Interface: RS232 - RS485 - SNMP - CAN (optional)
  • Environmental:
    • Temperature: 0°C ÷ 50°C
    • Non-condensing humidity: 0% ÷ 95%
    • Noise (at 1 m): < 52 dB
    • Protection rating: IP20
  • Dimensions (W x D x H - mm): 250 x 560 x 560 for MC-100/102, 250 x 660 x 560 for MC-104/106
  • Weight (kg): 60 for MC-100, 70 for MC-102, 83 for MC-104, 95 for MC-106
Compliance and Standards
  • UPS Classification: Class VI according to EN 62040-3
  • CE Marking: 2014/30/EU; 2014/35/EU
  • Compliance with standards: UPS: EN 60146-1-1, EN 62040-1-1, EN 62040-1-2, EN 62040-2, EN 62040-3, EN 60742; EMC: 2014/30/EU; Low voltage: 2014/35/EU
Contact Information
See more

Catalog excerpts

Technical Data ERIX Series-1

Technical Data ERIX Series MODEL Power - VA Input Phases Frequency Output Wave-form Harmonic distortion Protections Short-circuit EMI Suppression Signals LED Display Acoustic Computer interface Environmental Temperature Non-condensing humidity Noise (at 1 m) Protection rating Dimensions W x D x H - mm Weight - kg UPS Classification according EN 62040-3 CE Marking Compliance with the standards Frequency Overload Static switch mains-ups Batteries Type No. Batteries Vdc Voltage Restored energy time Stored energy time - min Sealed lead-acid (NiCd on request) 2 (12 V 44 Ah) 3 (12 V 44 Ah) 24 36 8 hours for 90% charge level 40 Overload, overtemperature, min/max battery voltage, min/max input voltage, min/max inverter voltage, synchronism With fuse on mains, with electronic protection on inverter EMI/RFI Filter Mains, Output, Battery, Overload, Fault Optional Battery mode, low battery, overload, overtemperature, fault RS232 - RS485 - SNMP - CAN (optional) 0°C ÷ 50°C 0% ÷ 95% < 52 dB IP20 250 x 560 x 560 60 Factory - Head Office S.P. km 5,3 C/da San Cusumano - 91100 Trapani - Italy Tel. +39 0923 562794 - Fax +39 0923 567880 Https://www.layer.it - E-mail: layer@la

 Open the catalog to page 1

All Layer Electronics catalogs and technical brochures

  1. Futura

    7  Pages

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.