1. Catalogs
  2. Layer Electronics
  3. Technical Data CS series

Technical Data CS series

Technical Data CS series

Product catalog summary
Technical Specifications
  • Models: CS-2, CS-3, CS-3/1
  • Power: 600 VA, 1000 VA, 1500 VA respectively
  • Input: Single-phase, Voltage 220/230/240 V ± 20% (other voltages on request), Frequency 50/60 Hz ± 10%
  • Output: Sine wave, Harmonic distortion < 3%, Voltage 220/230/240 V ± 1% (other voltages on request), Frequency 50/60 Hz ± 0.5%
  • Overload Capacity: 105% for 10 sec., 130% for 300 ms
Batteries
  • Type: Sealed lead-acid (NiCd on request)
  • Number: 2 (12 V 44 Ah)
  • Voltage: 24 Vdc
  • Restored Energy Time: 3 hours for 90% charge
  • Stored Energy Time: 90 min for CS-2, 40 min for CS-3/CS-3/1
Protections
  • Overload, overtemperature, min/max battery voltage, min/max input voltage, min/max inverter voltage, synchronism
  • Short-circuit protection with fuse on mains and electronic protection on inverter
  • EMI Suppression with EMI/RFI Filter
Signals
  • LED indicators for Mains, Output, Battery, Overload, Fault
  • Optional Display
  • Acoustic signals for Battery mode, low battery, overload, overtemperature, fault
  • Computer interface options: RS232, RS485, SNMP, CAN
Environmental Conditions
  • Temperature: 0°C to 50°C
  • Humidity: 0% to 95% non-condensing
  • Noise Level: < 52 dB at 1 m
  • Protection Rating: IP20
Physical Dimensions and Weight
  • Dimensions (W x D x H): 450 x 250 x 650 mm for CS-2, 550 x 250 x 750 mm for CS-3/CS-3/1
  • Weight: 65 kg for CS-2, 75 kg for CS-3, 85 kg for CS-3/1
Compliance and Standards
  • UPS Classification: Class VFI according to EN 62040-3
  • CE Marking: 2014/30/EU; 2014/35/EU
  • Standards Compliance: EN 60146-1-1, EN 62040-1-1, EN 62040-1-2, EN 62040-2, EN 62040-3, EN 60742; EMC: 2014/30/EU; Low voltage: 2014/35/EU
Contact Information
See more

Catalog excerpts

Technical Data CS series-1

Technical Data CS series MODEL Power - VA Input Phases Voltage Frequency Output Wave-form Harmonic distortion Voltage Frequency Overload Batteries Type No. Batteries Vdc Voltage Restored energy time Stored energy time - min Protections Short-circuit EMI Suppression Signals LED Display Acoustic Computer interface Environmental Temperature Non-condensing humidity Noise (at 1 m) Protection rating Dimensions W x D x H - mm Weight - kg UPS Classification according EN 62040-3 CE Marking Compliance with the standards Sealed lead-acid (NiCd on request) 2 (12 V 44 Ah) 24 3 hours for 90% charge level 90 40 Overload, overtemperature, min/max battery voltage, min/max input voltage, min/max inverter voltage, synchronism With fuse on mains, with electronic protection on inverter EMI/RFI Filter Mains, Output, Battery, Overload, Fault Optional Battery mode, low battery, overload, overtemperature, fault RS232 - RS485 - SNMP - CAN (optional) 0°C ÷ 50°C 0% ÷ 95% < 52 dB IP20 450 x 250 x 650 65 Factory - Head Office S.P. km 5,3 C/da San Cusumano - 91100 Trapani - Italy Tel. +39 0923 562794 - Fax +39 0923 567880 Https://www.layer.it - E-mail: layer@la

 Open the catalog to page 1

All Layer Electronics catalogs and technical brochures

  1. Futura

    7  Pages

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.