CUSTOMCONTROLSENSORS

CUSTOMCONTROLSENSORS

CUSTOMCONTROLSENSORS

Product catalog summary
Description:
The 6900GE*K** Adjustable Pressure Switch is designed for hazardous areas, featuring a Turck® electrical connection for easy installation in Class I, Division 2 applications. It offers superior ingress protection and does not require an electrical junction box. The device is highly reliable, utilizing the CCS Dual-Snap® Belleville disc spring principle, and is based on aerospace technology. It is compact, internally adjustable, and resistant to vibration and shock, with a high cycle life and over-pressure capability. The electrical assembly is hermetically sealed for environmental protection.
Specifications:
- Shipping Weight: Approximately 18 ounces (510 grams)
- Adjustable Set Point Range: 1 to 3400 PSIG (0.07 to 234 bar, 6.89 to 23400 kPa)
- Operating Temperature: -40° to 176°F (-40° to 80°C), varies with O-ring selection
- Certifications: CE Mark, CRN, Dual Seal ANSI/ISA-12.27.01, NACE MR0175/ISO 15156, NEMA 4, 7, 9, 13/IP66, U.L./cUL
- Wetted Parts: Aluminum pressure port, polyimide diaphragm, Buna N O-ring
Installation and Adjustment:
To adjust the set point, loosen the access cover and use a screwdriver to adjust the screw. Attach to a variable pressure source with a suitable gauge to check circuit continuity at desired pressures. Turn clockwise to increase settings and counterclockwise to decrease. Do not use the electrical hex for torquing.
Operating and Ordering Data:
The series includes models with varying adjustable set point ranges, system pressures, and proof pressures. Options for wetted parts include aluminum and stainless steel, with various O-ring materials available.
Electrical Characteristics:
The switch element is rated for SPST, SPDT, and DPST configurations with specific voltage and amperage ratings. Gold contacts are available as an option.
Ordering Instructions:
Specify the series based on required set point, range, dead band, system pressure, and proof pressure. Add desired options and wiring code, followed by the applicable standard suffix number.
Certifications:
The device is UL listed for hazardous locations and rated for Class I, Division 2, Groups A, B, C, or D. Consult the CCS website for a complete certification and approval listing.
See more

Catalog excerpts

CUSTOMCONTROLSENSORS-1

Hazardous Areas Adjustable Pressure Switch DESCRIPTION 6900GE*K** - Diaphragm Sensor with Turck® Connector SERIES: 6900GE* 6900GZE* • Turck® electrical connection for easy “plug and play” in Class I, Division 2 applications ADJUSTABLE • Turck® connector provides superior ingress SET POINT RANGE: protection 1 to 3400 PSIG • No electrical junction box required. 0.07 to 234 bar • Highly reliable devices utilizing the 6.89 to 23400 kPa CCS Dual-Snap® Belleville disc spring principle pioneered by CCS’ engineers. • Engineering based on aerospace technology. OPERATING TEMPERATURE: Temperature limits change with O-ring selection. • Rigid, compact and internally adjustable for -40° to 176°F convenient field set point adjustment. -40° to 80°C • Repeatable and stable set points. • Vibration and shock resistant. STANDARD FEATURES: • High cycle life. • CE Mark • High over-pressure capability. • CRN (System and Proof) • Dual Seal: ANSI/ISA-12.27.01 • NACE MR0175 / ISO 15156 • Hermetically sealed electrical assembly for • NEMA: 4, 7, 9,13 / IP66 environmental protection. SHIPPING WEIGHT: APPROXIMATELY 18 OUNCES (510 GRAMS) INSTALLATION DRAWING 1.00 HEX (25,4 mm) ELECTRICAL CONNECTION 7/8-16 UN MALE THREADS 4 OR 6 MALE PINS U.L. / cUL Hermetically Sealed Electrical Assembly 316 SST Electrical Assembly DESIGN PRINCIPLES 6900GZEK**-7066 FLUSH MOUNT CONFIGURATION SHOWN BELOW (-7074 FLUSH MOUNT HASTELLOY) UL & cUL CERTIFIED PRODUCT ADJUSTMENT WHEEL (2) MOUNTING HOLES .210 (5,3 mm) DIAMETER 1.125 (28,6 mm) 1.25 HEX (31,8 mm) DIAPHRAGM IS FLUSH WITH THIS SURFACE *See Installation & Maintenance Instructions 10-1228 FIELD SETTING: Loosen access cover. Adjust adjustment screw using screwdriver slot as illustrated, then attach to a variable pressure source with a suitable gage, and check that the circuit continuity operates at the pressures desired. Clockwise to increase settings. Counterclockwise to decrease setting. NOTE: DO NOT USE ELECTRICAL HEX FOR TORQUING.

 Open the catalog to page 1
CUSTOMCONTROLSENSORS-2

O PERATING AND ORDERING DATA Hazardous Areas Adjustable Pressure Switch 6900GE*K** - Diaphragm Sensor with Turck® Connector 1. Specify the series based on your required set point, range, dead band, system pressure and proof pressure. 2. Add desired options model code letter (*). 4. Add the applicable standard suffix number. (Ex: 6900GCEK4D12-7044) PRESSURE CONVERSION 1 BAR = 14.5 PSI 1 kPa = 0.145 PSI OPTIONS MODEL CODES (*) A: Viton® O-Ring (STD on GZE models) C: + Suffix for Different Welded Capsule Materials F: Ethylene Propylene O-Ring OPTIONAL STANDARD MODIFIED SUFFIXES 7008: Gold Contacts 7042:...

 Open the catalog to page 2

All CCS (CUSTOM CONTROL SENSORS) catalogs and technical brochures

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.